The Indoor Air
Quality Procedure

IAQP revolutionizes ventilation design by
enabling energy efficiency and promoting
safer indoor environments.

What is the Indoor Air Quality Procedure?

The Indoor Air Quality Procedure is an alternative to the widely used Ventilation Rate Procedure (VRP) for determining the design rate of outdoor airflow necessary to maintain acceptable indoor air quality. The IAQP design ensures that concentrations of design compounds such as formaldehyde, PM2.5, and ozone, in the indoor environment are kept below their design limits, as specified in Table 6-5 of ASHRAE Standard 62.1-2022. This is achieved through a combination of source control and the purification of recirculated air.

Key Benefits

Health and Safety

Identifying and eliminating harmful contaminants in indoor air reduces the risk of health problems for building occupants, thus creating a safer and healthier indoor environment.

Energy Savings

Effectively reduce the intake and conditioning of polluted Outside Air (OA) by 50%-90%.

Lower Costs

Reduced ventilation allows for a reduction in HVAC equipment capacity and lower operational costs.

Liability Mitigation

The reduction in pollutants and health risks minimizes potential legal financial liabilities.

Compliance

Maintains compliance with ASHRAE Standard 62.1-2022 and supports ASHRAE Standard 241 and qualification for LEED credits.

Ventilation Methods Comparison

ASHRAE Table 6-5

Design Compounds and their Design Limits

Compound or PM2.5 Cognizant Authority Design Limit
Acetaldehyde Cal EPA CREL (June 2016) 140 µg/m3
Acetone AgBB LCI 1200 µg/m3
Benzene Cal EPA CREL (June 2016) 3 µg/m3
Dichloromethane Cal EPA CREL (June 2016) 400 µg/m3
Formaldehyde Cal EPA 8-hour CREL (2004) 33 µg/m3
Naphthalene Cal EPA CREL (June 2016) 9 µg/m3
Phenol AgBB LCI 10 µg/m3
Tetrachloroethylene Cal EPA CREL (June 2016) 35 µg/m3
Toluene Cal EPA CREL (June 2016) 300 µg/m3
1,1,1-Trichloroethane Cal EPA CREL (June 2016) 1000 µg/m3
Xylene, total AgBB LCI 500 µg/m3
Carbon monoxide U.S. EPA NAAQS 9 ppm
Particulate matter (PM2.5) U.S. EPA NAAQS (annual mean) 12 µg/m3
Ozone U.S. EPA NAAQS 70 ppb
Ammonia Cal EPA CREL (June 2016) 200 µg/m3

Climate Zones in the IAQP

Using the VRP can make ventilation very costly depending on your climate zone.

Air Cleaning in the IAQP

Adding air cleaners to ventilation design allows for energy reduction through the use of
recirculated and purified air, thus reducing the intake of outdoor air while maintaining all
design compounds within the building under their design limits.

The Indoor Air Quality Verification

Preliminary assessment of occupant satisfaction and indoor design compound concentration measurements need to be performed to verify that design limits are met. For each design compound and PM2.5, the emission rates from indoor sources such as, occupants, building materials, furnishings, and equipment shall be determined. An additional verification test, and annually thereafter, must be conducted to verify that design compounds remain under their design limits after the IAQP has been deployed.

Assessment and Verification Requirements

Allowed Laboratory Test Methods for the IAQP Verification Testing

 

Compound Allowed Test Methods
VOCs except formaldehyde, acetaldehyde, and acetone ISO 16000-6; EPA TO-17; ISO 16017-1; ISO 16017-2; ASTM D6345-10
Formaldehyde, acetaldehyde, and acetone ISO 16000-3; EPA IP-6; ASTM D5197
Carbon monoxide ISO 4224; EPA IP-3

Direct Reading Instruments Minimum Specifications for the IAQP Verification Testing

 

  Ozone PM2.5 Carbon Monoxide
Accuracy (±) 5 ppb Greater of 5 µg/m³ or 20% of reading Greater of 3 ppm or 20% of reading
Resolution (±) 1 ppb 5 µg/m³ 1 ppm

 

Number of Measurement Points for the IAQP Verification Testing

 

Total Occupied Floor Area, ft² (m²) Number of Measurements
≤25,000 (2500) 1
>25,000 (2500) and ≤50,000 (5000) 2
>50,000 (5000) and ≤100,000 (10,000) 4
>100,000 (10,000) 6

Achieve ASHRAE Standard 62.1 and 241
Compliance With AirBox Air Cleaners

AirBox air cleaners are specifically engineered to abide by the strict indoor air quality requirements set forth by both ASHRAE Standard 241 for heightened infectious risk and ASHRAE Standard 62.1-2022 Indoor Air Quality Procedure for standard operation.

By harnessing advanced air purification technologies, AirBox systems effectively capture over 99.99% of tested airborne contaminants,
including infectious aerosols that can pose significant health risks. Tests are available on request.

AirBox air cleaners apply to a wide range of building types, including corporate offices, construction sites, schools, and healthcare facilities.

AirBox Maintains Compliance

Professional Analysis

Our data-driven Air Quality Assessment
takes the guesswork out of what’s going
on with your air. It tells you exactly what
contaminants are in your indoor air and
how much. These steps will lead you
from guessing to knowing – and from
dirty, unhealthy air to clean.

Asset Protection

By ensuring good indoor air quality, the
HVAC system can operate more
efficiently, reducing energy costs and
extending its lifespan. This, in turn, can
also lower the maintenance costs for
your building.

Risk and Liability Mitigation

Building owners and managers have a
legal responsibility to provide a safe
and healthy environment for their
occupants. Failure to maintain proper
IAQ can result in serious liability risks,
including lawsuits, fines, and damage to
the reputation of the building.

Ready to convert to the IAQP and save energy?

Partnering with a trusted name like AirBox ensures that you’re not only compliant with
ASHRAE Standards, but also providing the best environment for your occupants.